Hammerschlag & Joffe

Feeder Size Calculator

Internal Tool
Purpose

Conductor and conduit fill sizing tool. For final sizing, verify against the current Canadian Electrical Code.

Inputs


Voltage drop inputs (optional)

Results

Copper

Selected Conductor Size
Table Used
Ampacity per Conductor (A)
Bonding / Ground (Table 16)
Conduit Trade Size
Suggested Size

Aluminum

Selected Conductor Size
Table Used
Ampacity per Conductor (A)
Bonding / Ground (Table 16)
Conduit Trade Size
Suggested Size

Checks


Voltage drop check

Approximate voltage drop check. Enter length to calculate. Default limit is 3%.

Copper

Voltage Drop
Meets Limit?
Suggested Size (to meet voltage drop limit)

Aluminum

Voltage Drop
Meets Limit?
Suggested Size (to meet voltage drop limit)

Conduit fill summary

Fill % (Table 8)
Total Conductors per Run (for fill)

Copper

Area per Conductor (mm²)
Total Conductor Area (mm²)
Max Conduit Fill (mm²)
Remaining Fill %
Ground Area (insulated, mm²)

Aluminum

Area per Conductor (mm²)
Total Conductor Area (mm²)
Max Conduit Fill (mm²)
Remaining Fill %
Ground Area (insulated, mm²)

Conduit fill areas (selected conduit type)

Trade sizes and maximum allowable fill for the selected conduit type and number of conductors in a single run.
Copper
Trade SizeMax Fill Area (mm²)OK
Aluminum
Trade SizeMax Fill Area (mm²)OK

Underground: alternate parallel options

Shown only for Underground. Indicates what conductor size would be required if the number of parallel sets is changed.
Conductors/PhaseCu sizeAl size
Voltage drop calculation – assumptions & method

The voltage drop shown in this tool is an approximate design check intended for preliminary feeder sizing. It is not a substitute for a detailed voltage drop study.


Calculation basis

Voltage drop equations
  • I = total load current
  • cosθ = entered power factor (PF)
  • sinθ = √(1 − PF²)
  • Length = one‑way conductor length

Resistance (R)

  • Calculated from conductor cross‑sectional area derived from selected AWG or kcmil size
  • Material resistivity based on typical copper or aluminum values at ~75 °C
  • For parallel runs, resistance is divided equally among sets

Reactance (X)

  • Assumed constant value of 0.08 Ω/km
  • Independent of conductor size, spacing, or conduit type
  • Divided equally for parallel runs

Additional assumptions

  • Skin effect and proximity effect are not explicitly modeled
  • Installation‑specific impedance variations are not considered

Design voltage drop vs CEC recommendations

This calculator reports design voltage drop for engineering evaluation. The Canadian Electrical Code provides recommended voltage drop limits (commonly cited as feeders typically ≤ 3%), but these are guidance values rather than absolute limits. Final acceptance should consider equipment tolerances, starting conditions, and project‑specific criteria.

Always verify final conductor sizing and voltage drop against the current Canadian Electrical Code, project specifications, and manufacturer requirements.